to main content Automatic Transfer Switch (ATS) transfer time requirements - Testing | Nursing Care Center | Environment of Care EC | The Joint Commission
Automatic Transfer Switch (ATS) transfer time requirements - Testing

What is the requirement for testing essential electrical system transfer switches (automatic and manual)?

Any examples are for illustrative purposes only.

The Joint Commission standard EC.02.05.07 EP7 requires that all automatic transfer switches are tested monthly. Testing activities are to be conducted in accordance with the manufacturer's instructions for use.  There must be documentation of the result. 

The monthly generator load test must include a complete simulated cold start along with automatic and manual transfer of all essential electrical system loads. It is best practice, but not a requirement, to initiate the load test with a different ATS each month.  

The weekly inspection of the emergency power supply system (EPSS) as per EC.02.05.07 EP 4 requires that all associated components and batteries be inspected which include all ATS, battery chargers, radiator, fuel pumps, etc. 

Each ATS is uniquely identified in the equipment inventory so that testing for each unique piece of equipment or device is tested to demonstrate that the testing and inspections have been completed as required. 

The essential electrical system must be maintained to supply emergency power within 10 seconds of loss of normal power. If the 10-second criteria is not met during regular testing, the organization must have a process to confirm on an annual basis that the 10-second criteria can be met. 

Reference: 
NFPA 99-2012, 6.4.4.1.1 
Manual: Nursing Care Center
Chapter: Environment of Care EC
Last reviewed by Standards Interpretation: October 25, 2021 Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on May 09, 2023 with update notes of: Review only, FAQ is current Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.