Manual:
Nursing Care Center
Chapter:
Environment of Care EC
Topic:
Inspection Reports - Fire Safety Format
What is the required format for fire safety system inspection reports?
Any examples are for illustrative purposes only.
The Joint Commission is not prescriptive to a specific format for fire safety system inspection records and reports. Standard EC.02.03.05/EP 28 specifies the required information that must be included on the report documenting the maintenance, testing, and inspection activities for fire alarm and fire protection systems.
The required information for each service record must include the following:
Additional Resources
NFPA 25-2011: 4.3; 4.4;
NFPA 72-2010: 14.2.1; 14.2.2; 14.2.3; 14.2.4.
The Joint Commission is not prescriptive to a specific format for fire safety system inspection records and reports. Standard EC.02.03.05/EP 28 specifies the required information that must be included on the report documenting the maintenance, testing, and inspection activities for fire alarm and fire protection systems.
The required information for each service record must include the following:
- Name of the activity
- Date of the activity
- Inventory of devices, equipment, or other items
- Required frequency of the activity
- Name and contact information, including affiliation, of the person who performed the activity
- NFPA standard(s) referenced for the activity (including the edition and section)
- Results of the activity
Additional Resources
NFPA 25-2011: 4.3; 4.4;
NFPA 72-2010: 14.2.1; 14.2.2; 14.2.3; 14.2.4.
Last updated on November 15, 2021
First Published Date: April 11, 2016