Eye Wash Station and Emergency Showers - Design Criteria

What is the design and operational criteria for eye wash stations and emergency showers?

Any examples are for illustrative purposes only.

Eyewash stations and emergency showers are flushing devices required in locations where workers are handling injurious corrosive or caustic chemicals.  Any chemicals that have a pH less than 2.0 or greater than 11.5.  Common corrosive chemicals used in health care, include but not limited to; glutaraldehyde, formaldehyde, bleach and sodium hydroxide (caustic soda). 

These flushing devices are required by the Occupational Safety and Health Administration (OSHA).  OSHA's requirements for emergency eyewashes and showers can be found in 29 CFR 1910.151(c): "Where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use." OSHA refers employers to ANSI Z358.1-2014.

Requirements of this standard for an eye wash station include:
  • assembled and installed in accordance with the manufacturer's instructions
  • in accessible locations that require no more than 10 seconds to reach. The eyewash shall be located on the same level as the hazard and the path of travel shall be free of obstructions (no doors) that may inhibit its immediate use
  • located in an area identified with a highly visible sign positioned so the sign shall be visible within the area served by the eyewash
  • area around the eyewash shall be well-lit
  • connected to a supply of flushing fluid to produce the required spray pattern for a minimum period of 15 minutes, 1.5 liters per minute (0.4 gallons per minute)
  • flushing fluid is tepid, 16 to 38 degrees Celsius (60 to 100 degrees Fahrenheit)
  • if the possibility of freezing conditions exists, the eyewash shall be protected from freezing or freeze-protected equipment shall be installed
  • if shut off valves are installed in the supply line for maintenance purposes, provisions shall be made to prevent unauthorized shut off
  • The actuating valve once activated the valve shall remain open without requiring further use of the operator's hands (single action operation)
Reference standard EC.02.02.01: The hospital minimizes risks associated with selecting, handling, storing, transporting, using, and disposing of hazardous chemicals.
Manual: Laboratory
Chapter: Environment of Care EC
Last reviewed by Standards Interpretation: August 09, 2023 Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on August 09, 2023 with update notes of: Review only, FAQ is current Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.