to main content Life Safety Floor Plan Content - Hazardous Materials | Hospital and Hospital Clinics | Life Safety LS | The Joint Commission
Life Safety Floor Plan Content - Hazardous Materials

What method is required to identify hazardous storage areas on life safety floor plans?

Any examples are for illustrative purposes only.

Portions of buildings that are considered hazardous by the definition of NFPA 101 (2012 edition) Life Safety Code, shall be identified on the life safety drawings per the requirements of LS.01.01.01 EP3.  There is no specific required method of identification.  Some organizations identify them with a symbol, some use a hatch overlay.  The method used should be shown on the drawing legend as identifying hazardous areas.

Even though many hazardous areas are required by code to have either 1-hr rated or smoke partition walls, it is not enough to simply have the walls of the hazardous area shown with the rating, as walls are often rated for other reasons.

The life safety drawings should also indicate whether the area is sprinkled and whether it is considered new or existing.  Facilities are classified as "existing" if final plans for construction, additions, renovations, or changes in occupancy were approved by the local authority having jurisdiction before July 5, 2016.  

Hazardous areas in health care occupancies are defined in Section 18.3.2 for new and 19.3.2 for existing.  Hazardous areas in ambulatory health care occupancies are defined in Section 20.3.2 for new and 21.3.2 for existing and refer to 38/39.3.2 (business occupancy) for requirements.
 
Manual: Hospital and Hospital Clinics
Chapter: Life Safety LS
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on October 27, 2021
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.