Means of Egress - Suite-to-Suite Exit/Suite Direct Exit to Stairwell

What is the requirement for suite-to-suite exits or suite direct exit to a stairwell?

Any examples are for illustrative purposes only.

Suites are groups of rooms that for the purposes of life safety, function as one big room.  The 2012 edition of NFPA 101 Life Safety Code lists the requirements for suites in health care occupancies at 18/19.2.5.7.  They are limited in size based on whether they are sprinkled, used for patient care, and used for sleeping.

Sleeping suites greater than 1000 square feet and patient care non-sleeping suites greater than 2500 square feet require two means of egress.  One of these means of egress shall be directly into a corridor, but the other means of egress may be into an adjacent suite, so long as the perimeter wall and door between the two suites meet corridor requirements (smoke resistive and the door must be positive latching).  Either of these required means of egress may be substituted with a door that goes directly into an exit stair, exit passageway, or exit door to the exterior.

Reference LS.02.01.20 EP 30 & 31 
Manual: Home Care
Chapter: Life Safety LS
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on October 26, 2021
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.