Medical Gas Cylinder Storage

Can various types of medical gas cylinders be stored comingled in the same storage room?

Any examples are for illustrative purposes only. 

NFPA 99 does not prohibit various medical gas cylinders from being stored in the same room as long as flammable and non-flammable gasses are not comingled.  Typical medical gases whose storage can be comingled with oxygen include: Carbon Dioxide, Medical Air, Nitrogen, Nitrous Oxide, Helium, Argon, and Xenon. All criteria as specified in EC.02.05.09 applies as well as NFPA 99-2012 11.6.5.2 requiring full and empty cylinders to be segregated from each other. 

As previously indicated, non-flammable medical gas cylinders cannot be comingled with; flammable materials, cylinders containing flammable gases, or containers containing flammable liquids. Typical flammable gases may include but are not limited to: Acetylene, Butane, Ammonia, Ethane, and Propane.  This prohibition is addressed in NFPA 99-2012; 5.1.3.2.4.

Medical gas cylinders are also not allowed to be stored in an enclosure containing motor driven devices with the exception of cylinders intended for instrument air reserve headers that must comply with NFPA 99-2012; 5.1.3.9.5. This reference can be found at NFPA 99-2012; 5.1.3.3.4.2

 
 
Manual: Home Care
Chapter: Environment of Care EC
Last reviewed by Standards Interpretation: October 22, 2021 Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: March 21, 2019 This Standards FAQ was first published on this date.
This page was last updated on May 09, 2023 with update notes of: Review only, FAQ is current Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.