to main content Inspection Reports - Fire Safety Format | Home Care | Environment of Care EC | The Joint Commission
Inspection Reports - Fire Safety Format

What is the required format for fire safety system inspection reports?

Any examples are for illustrative purposes only

The Joint Commission is not prescriptive to a specific format for fire safety system inspection records and reports. Standard EC.02.03.05/EP 28 specifies the required information that must be included on the report documenting the maintenance, testing, and inspection activities for fire alarm and fire protection systems.  

The required information for each service record must include the following:
  • Name of the activity
  • Date of the activity
  • Inventory of devices, equipment, or other items
  • Required frequency of the activity
  • Name and contact information, including affiliation, of the person who performed the activity
  • NFPA standard(s) referenced for the activity (including the edition and section)
  • Results of the activity
A common issue during the survey process is that the organization is not adequately familiar with the content of the report and the configuration of their fire safety systems. An effective way to accomplish this is for the testing entity to closely review the report with the organization's representative. 

Additional Resources
NFPA 25-2011: 4.3; 4.4; 
NFPA 72-2010: 14.2.1; 14.2.2; 14.2.3; 14.2.4.
Manual: Home Care
Chapter: Environment of Care EC
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on November 15, 2021
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.