Fire Extinguishment Systems - Testing and Cleaning

What is the requirement for testing kitchen automatic fire extinguishing systems and cleaning requirements?

Any examples are for illustrative purposes only.

The Joint Commission references the 2011 edition of NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, where all actuation components, including remote manual pull stations, mechanical or electrical devices, detectors, actuators, and fire-actuated dampers, shall be checked for proper operation during the inspection in accordance with the manufacturer's listed procedures. This includes annual replacement of the fusible link.

The Joint Commission is not prescriptive for the procedures to be used to clean and maintain kitchen extinguishing systems. The organization is expected to have a plan in place for cleaning based upon the manufacturer's instructions for use.

The organization must also be able to demonstrate on-going compliance with required system design components described in LS.02.01.35 that include:
  • portable fire extinguishers in the vicinity
  • grease removal devices
  • fire alarm system activation
  • deactivation of the cooking fuel source
  • proper operation of the exhaust system
Manual: Home Care
Chapter: Environment of Care EC
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on May 09, 2023 with update notes of: Editorial changes only Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.