Exit Signage - Internal Illumination

What are the requirements for photoluminescent Exit signs?

Any examples are for illustrative purposes only

Where an exit sign is required, they may be either externally illuminated or internally illuminated.

Photoluminescent signs are a type of internally illuminated exit sign sometimes used to mark the means of egress, and as such, must meet certain criteria to ensure that they are reliable and readable by occupants of the facility.  Using photoluminescence, light is absorbed from the surroundings onto the sign surface, stored and then re-emitted, making the signs glow when the building is dark.  

NFPA 101 (2012 edition) The Life Safety Code, Section 7.10.7.2 requires that "the face of a photoluminescent sign shall be continually illuminated while the building is occupied.  The illumination levels on the face of the photoluminescent sign shall be in accordance with its listing.  The charging illumination shall be a reliable light source, as determined by the authority having jurisdiction.  The charging light source, shall be of a type specified in the product markings." Per Section 7.10.7.1, internally illuminated signs shall be listed in accordance with ANSI/UL 924, Standard for Emergency Lighting and Power Equipment.

Some jurisdictions require photoluminescent egress path markers, typically in high-rise buildings.  It should be noted that these signs may not meet the requirements of exit signs and are used in addition to, but not in place of exit signs.  

Reference LS.02.01.20 EP38, EP40 
Manual: Critical Access Hospital
Chapter: Life Safety LS
Last reviewed by Standards Interpretation: July 12, 2023 Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on July 12, 2023 with update notes of: Review only, FAQ is current Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.