to main content Operating Room - Temperature | Critical Access Hospital | Environment of Care EC | The Joint Commission
Operating Room - Temperature

Can temperatures be outside of established range in operating rooms?

Any examples are for illustrative purposes only.

The Joint Commission references NFPA 99-2012 Chapter 9, that requires the use of ASHRAE 170-2008, Ventilation Table 7-1.  This document provides allowances to exceed minimum temperature ranges.  To use this exception, it must be done by following the established organizational policy.  In accordance with the allowances, the policy or formal process must be limited to cases based on either surgeon, patient, or procedure. It is not acceptable to consistently maintain temperatures outside of the required ranges.
 
This is not a blanket exception but one to be used on a case-by-case basis.  Once the surgical procedure has been completed the temperature is to be returned to the normal range.   Additionally, when the temperature is temporarily adjusted outside of the established range, there is still an expectation that relative humidity levels remain below 60%.  

Reference EC.02.05.01 EP 15 
Additional Resources:
A read only copy of the ASHRAE standard can be accessed from this hyperlink: ASHRAE
Then scroll down the list to Standard 170-2008 Ventilation of Health Care Facilities.
Manual: Critical Access Hospital
Chapter: Environment of Care EC
Last reviewed by Standards Interpretation: October 17, 2022 Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on May 09, 2023 with update notes of: Review only, FAQ is current Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.