to main content Generator - Monthly Load Test | Critical Access Hospital | Environment of Care EC | The Joint Commission
Generator - Monthly Load Test

What is the requirement for initiating and completing the monthly emergency generator load test?

Any examples are for illustrative purposes only.

The monthly emergency power system load test is to be initiated by a simulated or actual loss of normal electrical power.  

There are 2 methods both of which are acceptable means of initiating the monthly test:
  • A TEST Switch may be included on the automatic transfer switch (ATS) to simulate loss of normal power
  • Alternatively, a circuit breaker feeding an ATS is opened resulting in a loss of normal electrical power
In either case both will result in activating the starter for the generator and activation of the ATS transferring the load from normal power to emergency generator power.

The duration of the test is to be at least 30-continuous minutes with a minimum dynamic load of at least 30% of the nameplate rating.  The cool down period for the generator is not included as part of the 30-minute run time.

The monthly test is invalid if the generator is started and allowed to run for a period before activating the ATS to transfer the load to the generator.  This does not fully test the generators ability to respond in actual emergency conditions, which require sensing loss of normal power and providing emergency power within 10 seconds from a cold start.

Additional Resources
EC.02.05.07 EP 5 and EP 6
NFPA 99-2012: 6.4.4.1
Manual: Critical Access Hospital
Chapter: Environment of Care EC
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on October 26, 2021
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.