Fire Sprinkler System - "Fully Sprinklered"

What constitutes a facility being considered "fully sprinklered?" Occupancies

Any examples are for illustrative purposes only.

NFPA 13 (2012 edition) Standard for the Installation of Sprinkler Systems requires that "a building, where protected by an automatic sprinkler system installation, shall be provided with sprinklers in all areas except where specific sections of this standard permit the omission of sprinklers."  The installation requirements may be found in Chapter 8 of that document.

Sprinklers are permitted to be omitted from some skylights (see 8.5.7.1); some concealed spaces (See 8.15.1.2); some spaces under ground floors, exterior docks, and platforms (see 8.15.6); some exterior roofs, canopies, porte-cocheres, balconies, decks, or similar projections (see 8.15.7); and some electrical equipment rooms (see 8.15.10.3).  All of these exceptions have specific criteria that must be met in order to utilize them.

NFPA 101 (2012 edition) Life Safety Code allows some additional exceptions specific to Health Care Occupancies.  From Section 18/19.3.5.5:
"In Type I and Type II construction, alternative protection measures shall be permitted to be substituted for sprinkler protection without causing a building to be classified as nonsprinklered in specified areas where the authority having jurisdiction has prohibited sprinklers."

From Section 18/19.3.5.10:
"Sprinklers shall not be required in clothes closets or patient sleeping rooms in hospitals where the area of the closet does not exceed 6 sq ft, provided that the distance from the sprinkler in the patient sleeping room to the back wall of the closet does not exceed the maximum distance permitted by NFPA 13."

Reference LS.02.01.35
Manual: Behavioral Health
Chapter: Life Safety LS
Last reviewed by Standards Interpretation: July 12, 2023 Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on July 12, 2023 with update notes of: Review only, FAQ is current Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.