NFPA 99 - Edition Adoption Date

What is the requirement for retroactive compliance with NFPA 99-1999?

Any examples are for illustrative purposes only

Effective July 5, 2016, the Centers for Medicare and Medicaid (CMS) adopted the 2012 edition of NFPA 99, Health Care Facilities Code.  

Facilities in which final plans were approved by the Authority Having Jurisdiction (AHJ) before July 5, 2016, are considered "existing." Section 1.3 of NFPA 99 does not require retroactive compliance in existing facilities unless alteration, renovation, or modernization has occurred or any of the organization's controlling authorities have specific requirements.  Where a CMS Condition of Participation (CoP) or a Joint Commission Standard and Element of Performance (EP) refer to a specific requirement from NFPA 99, compliance is expected regardless of whether the facility is new or existing.
  • Example:  Section 5.1.4.8.4 of NFPA 99 requires that "Zone valve boxes shall be installed where they are visible and accessible at all times."  This requirement also applies to existing installations because the requirements are referenced in the language of EC.02.05.09 EP 11 and CMS Tag K909. 
For other NFPA 99 requirements that are not expressly identified in the language of a CoP or an EP, facilities will be held to the code requirements that were in effect at the time of construction and maintain compliance with that version.

The first NFPA 99 edition was published in 1984.  The 1999 edition was adopted by The Joint Commission and CMS in 2003. For the years between, use the edition required by the organization's controlling authority for health care construction. In order to be relieved of the 1999 edition requirements, the organization must know the applicable requirements of construction for their facilities.
Manual: Behavioral Health
Chapter: Environment of Care EC
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on May 09, 2023 with update notes of: Editorial changes only Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.