Manual:
Assisted Living Community
Chapter:
Life Safety LS
Topic:
Means of Egress - Dead-end Corridor Storage
Can dead-end corridors be used for storage or other uses?
Any examples are for illustrative purposes only.
Dead-end corridors may be used for storage only past the last door opening into the corridor so that it does not impede the means of egress. If combustible items are stored, the area used for storage is limited to a 50 square feet footprint.
Reference LS.02.01.20 EP14
Dead-end corridors may be used for storage only past the last door opening into the corridor so that it does not impede the means of egress. If combustible items are stored, the area used for storage is limited to a 50 square feet footprint.
Reference LS.02.01.20 EP14
Last updated on June 28, 2023
with update notes of: Review only, FAQ is current
First Published Date: April 11, 2016
Last Reviewed Date: June 28, 2023