Fire Rated Assemblies - Vision Panels

What is the requirement for proper fire rated vision panels?

Any examples are for illustrative purposes only.

For fire rated door assemblies in new horizontal exits, vision panels are required, according to section 18.2.2.5.6 of the Life Safety Code NFPA 101-2012.

If wired glass is used, and the vision opening is sized correctly according to NFPA 101-2012, Table 8.3.4.2 (does not exceed the area and dimension limits), then the wired glass is considered to be compliant. If glazed glass is used, regardless of whether the vision opening is sized correctly, the glass is to be labeled since that is the only way to determine if it is fire rated glass.
Manual: Assisted Living Community
Chapter: Life Safety LS
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on October 29, 2021
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.