to main content Fire Rated Assemblies - Compliance | Ambulatory | Life Safety LS | The Joint Commission
Fire Rated Assemblies - Compliance

What is considered an assembly within a fire rated door system?

Any examples are for illustrative purposes only.

NFPA 80 (2010 edition) Standard for Fire Doors and Other Opening Protectives defines a fire door assembly as "any combination of a fire door, a frame, hardware, and other accessories that together provide a specific degree of fire protection to the opening."

Assemblies include, but are not limited to, the following components:
  • Door frame
  • Latch set and/or lockset
  • Hinges
  • Strike plate
  • Door leaf including rating label
  • Closer
  • Glazing(glass) and glazing frame
  • Coordinator
  • Hinges
  • Astragal
  • Transoms or side lights
  • Gasketing
  • Protective Plates
  • Exit hardware
  • Flush Bolt
  • Door holder/release device
If a component of a fire rated assembly is changed, then the change must result in the overall assembly still being compliant for its fire rating designation.  Just because a component, in and of itself, has the appropriate rating designation, may not mean that the design of the resulting assembly of components has been accepted by the testing authority. 
For same-product replacement of individual components (such as replacing a broken door closer with a new closer), as long as the new component is listed for use with the door in question, then the door assembly remains compliant. If not, then the resulting altered assembly must be validated by a field study of the assembly by a qualified entity.

Reference LS.02.01.10 EP9 
Manual: Ambulatory
Chapter: Life Safety LS
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on October 29, 2021
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.