to main content Relocatable Power Taps - UL Requirements | Ambulatory | Environment of Care EC | The Joint Commission
Relocatable Power Taps - UL Requirements

Where can relocatable power taps (RPTs) be used and what are the UL requirements?

Any examples are for illustrative purposes only.

The use of a Relocatable Power Tap (RPT) or power strip is addressed by standard EC.02.05.01 EP 23.  These devices may also be called by other names such as power strips, multiple outlet connection and multiple outlet strip.  These devices are not to be confused or considered electrical extension cords.

Per Condition of Participation (CoP) §482.41(d)(2):
  • RPT in the patient care vicinity^ are only used on movable patient care medical equipment and are permanently attached to the equipment and meet UL 1363A or UL 60601-1.
  • RPT in the patient care vicinity may not be used for non-patient care electrical equipment, such as personal electronics, except in long-term care resident rooms that do not use patient care medical equipment.
  • assembled by qualified personnel and meet the conditions of NFPA 99: 10.2.3.6.
  • Power strips for non-patient care electrical equipment in the patient care rooms, but outside of the patient care vicinity, must meet UL 1363.
  • In non-patient care rooms, power strips meet other UL standards.
In addition to CMS requirements, the following NFPA code requirements also apply:
  • The RPT is permanently attached to the equipment assembly.
  • The sum of the ampacity of all appliances connected to the RPT does not exceed 75% of the ampacity of the flexible cord supplying the RPT.
  • The ampacity of the flexible cord is in accordance with NFPA 70, National Electrical Code.
  • The electrical and mechanical integrity of the assembly is regularly verified and documented.
For full text, refer to NFPA 99-2012: 10.2.3.6; 10.2.4; NFPA 70-2011: 400-8; 590.3(D); Tentative Interim Amendment (TIA) 12-5)

^ The "patient care vicinity" is defined as a space, within a location intended for the examination and treatment of patients, extending 6 feet beyond the normal location of the bed, chair, table, treadmill, or other device that supports the patient during examination and treatment and extending vertically to 7-foot 6-inches above the floor.  For full text refer to NFPA 99-2012: 3.3.139

Reference EC.02.05.01/EP 23
Manual: Ambulatory
Chapter: Environment of Care EC
Last reviewed by Standards Interpretation: June 07, 2023 Represents the most recent date that the FAQ was reviewed (e.g. annual review).
First published date: April 11, 2016 This Standards FAQ was first published on this date.
This page was last updated on June 07, 2023 with update notes of: Review only, FAQ is current Types of changes and an explanation of change type: Editorial changes only: Format changes only. No changes to content. | Review only, FAQ is current: Periodic review completed, no changes to content. | Reflects new or updated requirements: Changes represent new or revised requirements.
Was this response helpful?

If no, please comment on how we could improve this response.

If you have additional standards-related questions regarding this topic, please use the Standards Online Submission Form

Get Extra Help with Books and E-books

Browse our gallery of books and e-books to find trusted prep and readiness resources, practical checklists and toolkits, and resources on specialized health care topics.

Stay Informed with Online Education

Online education is the most convenient and cost-effective way to educate your staff and minimize expenses without the need to leave your organization.

Reach Your Safety Goals with eProducts

Assessing and sustaining compliance with accreditation standards or CMS CoPs can be a challenge, but it doesn’t have to be. Rely on our proven software solutions developed by our team of industry experts.

Can't Find What You're Looking For?

If you do not find an answer to your question, please contact the Standards Interpretation Group (SIG).

Note: To provide adequate support to those organizations that are either accredited/certified or seeking accreditation/certification, we will only answer those questions submitted by those organizations seeking accreditation/certification or currently accredited/certified by the Joint Commission. The Joint Commission no longer answers questions submitted by students or vendors. Thank you for your understanding.